Pengaruh pengoperasian sumber daya di bawah tegangan nominal terhadap susut teknis di PT. PLN UPJ Wonosari

HARYONO, Bambang Eko, Sarjiya, ST., MT., Ph.D

2010 | Tesis | S2 Magister Sistem Energi Elektrik

Jaringan yang baik adalah jaringan yang dapat menjamin kelangsungan penyaluran dan memberikan kepuasan bagi konsumen karena kualitasnya, baik dalam operasi normal maupun pada saat terjadi gangguan. Saat pembangki t mengalami de fi sit day a, kadang-kadang PLN penyaluran melakukan pengoperasian jaringan listrik dibawah tegangan nominal (brown-out). Brown-out dilakukan untuk tujuan menjamin kelangsungan penyaluran kepada konsumen, dengan meminimalkan jumlah pelanggan yang mengalami pemadaman. Namun brown-out mempunyai efek turunya kualitas, bila penurunan yang tegangan berlebihan akan mengganggu unjuk kerja peralatan elektronik, motor, unjuk kerja kWh meter dan juga mempengaruhi besaran susut teknis. Dengan program EDSA (Electrical Distribution and Transmission System Analysis), diperoleh gambaran luas pengaruh pengoperasian tegangan dibawah nominal. Dari hasil simulasi yang dilakukan, setiap penurunan tegangan 100 V disisi tegangan menengah 20 kV susut teknis turun 1%. untuk jenis beban impedansi tetap. Dengan tegangan diturunkan sampai 10% tegangan nominal, kesalahan ukur kWh meter bertambah positip ± 0,25% - 1,0% dibanding pada tegangan nominal. Dari hasil tersebut dapat memberikan gambaran seberapa besar pengaruh brown-out terhadap susut teknis, berapa prosen susut teknis total maupun tiap feeder yang terjadi dan berapa prosen susut teknis masih dapat diturunkan. Kata kunci brown-out, susut teknis, losses~

The good network is the network which can guarantee continuity of power supply and gives satisfaction to consumer due to the quality, either in normal operation or at fault condition. When deficit energy occurs in generator, sometime PLN carry-out the brown-out. Brown-out is performed for securing the system, which is by economizing energy usage, so that interruption of service doesn't occur to all customers, or at least it can lessen interruption area. But brown-out has effect lowering of quality of supply, if abundant voltage drop will influence the performances of electronic equipments, motor, kWh meter accuracy, and technical losses value. With program EDSA (Electrical Distribution and Transmission System Analysis), is obtained the image of brown out effect. From simulation is obtained every 100 volt decrease in medium voltage 20 kV produce 1% technical losses, for permanent impedance type. With 10% nominal voltage decrease will make mistake at kWh meter increases positive ± 0, 25% - 1, 0% compared to at nominal voltage. From the result can describe how big the influence of brown-out to technical losses, how many percents total technical losses can occur in each feeder and how many percents technical losses should be able degraded. Keywords brown-out, technical losses, losses

Kata Kunci : Brown,out,Susut teknis,Losses

  1. S2-FKU-2010-Romano_A__Viegas-ABSTRACT.pdf  
  2. S2-FKU-2010-Romano_A__Viegas-BIBLIOGRAPHY.pdf  
  3. S2-FKU-2010-Romano_A__Viegas-TABLEOFCONTENT.pdf  
  4. S2-FKU-2010-Romano_A__Viegas-TITLE.pdf