Analisis Karakteristik Corona Discharge pada Berbagai Tipe Lightning Air Termination

Zuhdi Mubarak, Mochammad Wahyudi, S.T., M.T. ; Dr. Ir. Avrin Nur Widiastuti, S.T., M.Eng., IPM.,

2026 | Skripsi | TEKNIK ELEKTRO

Penelitian ini bertujuan untuk menganalisis fenomena corona discharge pada tiga jenis terminasi udara, yaitu Franklin rod, Early Streamer Emission (ESE) System 1000, dan Dynasphere System 3000 dengan tiga varian bentuk ujung (lancip, semi tumpul, dan tumpul). Pengujian dilakukan menggunakan sumber tegangan tinggi DC negatif dengan jarak antara pelat elektrode dan ujung lightning air termination sebesar 10 cm. Hal-hal yang diamati meliputi pola cahaya korona, bunyi korona, serta tegangan saat bunyi korona mulai terdengar. Pengamatan dilakukan di dalam ruang gelap dan didokumentasikan menggunakan kamera mirrorless.

Hasil penelitian menunjukkan bahwa setiap jenis terminasi udara memiliki karakteristik korona yang berbeda. Pada Franklin rod, cahaya dan bunyi korona mulai muncul pada tegangan 18 kV. Pada ESE System 1000, korona mulai muncul pada 30 kV. Pada Dynasphere System 3000, cahaya korona baru muncul pada 59 kV untuk varian ujung lancip, sedangkan varian ujung semi tumpul dan tumpul tidak menghasilkan cahaya korona sama sekali hingga batas pengujian maksimum 70 kV. Perbedaan ini berkaitan dengan pengaruh bentuk ujung elektroda terhadap kekuatan medan listrik di sekitarnya.

Penelitian ini menunjukkan bahwa pengamatan corona discharge menggunakan tegangan tinggi DC dapat menjadi salah satu cara alternatif untuk mempelajari perilaku terminasi udara terhadap medan listrik, terutama di laboratorium yang tidak memiliki generator impuls berukuran besar. Hasil penelitian ini diharapkan dapat menjadi salah satu referensi untuk pengamatan corona discharge pada terminasi udara proteksi petir.

This research aims to analyze the corona discharge phenomenon on three types of lightning protection, namely Franklin rod, Early Streamer Emission (ESE) System 1000, and Dynasphere System 3000 with three tip shape variants (sharp, semi-blunt, and blunt). Testing was carried out using a negative DC high-voltage source with a 10 cm gap between electrodes. The things observed were the corona light pattern, the corona sound, and the voltage at which the corona sound started to be heard (Corona Inception Voltage or CIV). Observations were made in a dark   room and documented using a mirrorless camera. 

The results showed that each type of air terminal has different corona characteristics. On the Franklin rod, corona light and sound started to appear at 18 kV. On the ESE System 1000, corona started to appear at 30 kV. On the Dynasphere System 3000, corona light only appeared at 59 kV for the sharp tip variant, while the semi-blunt and blunt tip variants did not produce any corona light up to the maximum test limit of 70 kV. This difference is related to the effect of the electrode tip shape on the strength of the electric field around it. 

This research shows that observing corona discharge using DC high voltage can be one alternative laboratory method to study the behavior of air terminals under an electric field, especially in laboratories that do not have large impulse generators. The results of this research are expected to be one of the initial references for observing corona discharge on lightning protection air terminals.

Kata Kunci : terminasi udara, Franklin rod, ESE System 1000, Dynasphere System 3000, corona discharge, proteksi petir, tegangan tinggi DC