Analisis Ground Potential Rise Akibat Arus Petir pada Mesh Grounding Menggunakan Metode FEM dan PEEC
Wizha Shandy, Mochammad Wahyudi, S.T., M.T.; Prof. Ir. Tumiran, M.Eng., Ph.D., IPU.
2026 | Skripsi | TEKNIK ELEKTRO
Petir dapat menimbulkan kenaikan potensial tanah (Ground Potential Rise/GPR) yang membahayakan manusia dan peralatan melalui tegangan sentuh (touch voltage) dan tegangan langkah (step voltage). Efektivitas sistem pentanahan sebagai jalur pelepasan arus petir dipengaruhi oleh konfigurasi mesh, kedalaman penanaman, dan resistivitas tanah. Penelitian ini membandingkan kinerja Finite Element Method (FEM) dan Partial Element Equivalent Circuit (PEEC) dalam menganalisis disipasi arus petir pada system mesh grounding melalui simulasi numerik menggunakan ANSYS Maxwell 3D (FEM) dan XGSLab modul XGSA_FD (PEEC).
Sistem pentanahan dimodelkan sebagai mesh seragam 40 × 60 m pada kedalaman 0,6 m dengan resistivitas tanah 200 ?.m. Arus petir impuls 10/350 µs dengan Ipeak 20 kA diinjeksikan pada titik tengah mesh; ANSYS Maxwell merepresentasikannya secara penuh dalam domain waktu, sedangkan XGSLab menggunakan Equivalent Sine Method (feq = 25 kHz, Irms = 14.140 A). Touch voltage dan step voltage dievaluasi menggunakan XGSLab mengacu pada IEC/TS 60479-1:2018.
Hasil menunjukkan pola sebaran GPR kedua metode serupa, menyebar merata dari titik injeksi menuju batas kalkulasi. Tegangan maksimum pada titik injeksi sebesar 26.086 V (ANSYS Maxwell) dan 28.460 V (XGSLab), selisih 2.374 V (±9,1%) akibat perbedaan domain analisis. Touch voltage berkisar 985,15–8.672,34 V dan step voltage 10,90–329,30 V. Step voltage masih di bawah batas aman ±17.730 V sehingga desain aman, namun touch voltage pada sebagian besar area melampaui batas aman ±1.414 V hingga 6,1 kali lipat, sehingga sistem pentanahan belum aman terhadap bahaya tegangan sentuh dan memerlukan mitigasi tambahan, seperti lapisan kerikil (surface layer) atau peningkatan kerapatan konduktor mesh pada area berisiko.
Lightning can cause Ground Potential Rise (GPR), which endangers humans and equipment through touch voltage and step voltage. The effectiveness of a grounding system as a path for dissipating lightning current is influenced by mesh configuration, burial depth, and soil resistivity. This study compares the performance of the Finite Element Method (FEM) and the Partial Element Equivalent Circuit (PEEC) method in analyzing lightning current dissipation in a mesh grounding system through numerical simulation using ANSYS Maxwell 3D (FEM) and XGSLab’s XGSA_FD module (PEEC).
The grounding system was modeled as a uniform 40 × 60 m mesh at a depth of 0.6 m with a soil resistivity of 200 ?.m. A 10/350 µs lightning impulse current with Ipeak of 20 kA was injected at the center point of the mesh; ANSYS Maxwell fully represents it in the time domain, while XGSLab uses the Equivalent Sine Method (feq = 25 kHz, Irms = 14,140 A). Touch voltage and step voltage were evaluated using XGSLab, referring to IEC/TS 60479-1:2018.
The results show similar GPR distribution patterns for both methods, spreading evenly from the injection point toward the calculation boundary. The maximum voltage at the injection point was 26,086 V (ANSYS Maxwell) and 28,460 V (XGSLab), a diffe rence of 2,374 V (±9.1%) due to differences in the analysis domain. Touch voltage ranges from 985.15–8,672.34 V and step voltage from 10.90–329.30 V. The step voltage remains below the safety threshold of ±17,730 V, so the design is safe, but touch voltage in most areas exceeds the safety threshold of ±1,414 V by up to 6.1 times, indicating that the grounding system design is not yet safe against touch voltage hazards and requires addi tional mitigation, such as a gravel surface layer or increased mesh conductor density in high-risk areas.
Kata Kunci : Grounding, Petir, FEM, PEEC, Ground Potential Rise