Analisis Sistem Distribusi Tenaga Listrik SMA Taruna Nusantara Pasca Revitalisasi Penyulang SGN11 dan SGN03 Berbasis Aliran Daya, Kontingensi, dan Stabilitas Tegangan-Frekuensi
Anggagar Bimo Priyambodo, Ir. Ma’un Budiyanto, S.T., M.T., IPU
2026 | Tugas Akhir | D4 TEKNOLOGI REKAYASA ELEKTRO
SMA Taruna Nusantara merupakan kawasan pendidikan asrama berstatus VVIP yang menuntut keandalan dan kontinuitas pasokan listrik tinggi, sehingga sistem distribusi tenaga listrik kawasan ini direvitalisasi dari konfigurasi radial sumber tunggal menjadi sistem penyulang ganda. Proyek Akhir ini bertujuan menganalisis dan membandingkan performa sistem distribusi tenaga listrik kawasan tersebut pada kondisi sebelum dan pasca revitalisasi melalui empat kajian, yaitu analisis aliran daya, kontingensi N-1, stabilitas tegangan berbasis kurva P-V, dan stabilitas frekuensi, yang disimulasikan menggunakan perangkat lunak DIgSILENT PowerFactory 2021 SP2. Hasil analisis aliran daya menunjukkan kedua sistem memenuhi standar, dengan tegangan bus berada dalam rentang 0,90–1,05 pu sesuai SPLN 1:1995. Pembebanan saluran tertinggi sebelum revitalisasi sebesar 63,87% pada saluran Trf1 - Perkantoran dan pasca revitalisasi sebesar 62,59% pada saluran Trf1 - Balairung, keduanya di bawah batas 80% sesuai SE Direksi PLN No. 0017.E/DIR/2014. Analisis kontingensi N-1 memperlihatkan dampak nyata revitalisasi, sebelum revitalisasi genset 400 kVA hanya mampu menyuplai Bus Perkantoran saat SGN11 lepas, sedangkan pasca revitalisasi ACOS TR secara otomatis mengalihkan suplai ke genset 1.000 kVA dalam 0,5 detik sehingga seluruh bus kawasan tetap tersuplai dengan tegangan 0,993–0,999 pu dan pembebanan tertinggi 62,26% pada saluran Genset - Balairung. Analisis stabilitas tegangan menunjukkan penguatan ketahanan tegangan yang signifikan pada sistem pasca revitalisasi, ditandai dengan naiknya beban titik nose point dari 0,93–1,84 MW menjadi 5,49–5,59 MW dan mengecilnya nilai perbandingan (M) dari 6,07%–7,36% menjadi di bawah 3%, sehingga sistem semakin aman terhadap keruntuhan tegangan (voltage collapse). Analisis stabilitas frekuensi menunjukkan kedua sistem mampu memulihkan frekuensi ke 50 Hz dengan nilai nadir yang memenuhi batas minimum ? 47,0 Hz sesuai Permen ESDM No. 20/2020, dengan nadir 49,006 Hz pada sistem sebelum revitalisasi melalui perpindahan manual sekitar 3 menit, dan nadir 48,45 Hz pada sistem pasca revitalisasi melalui perpindahan otomatis 0,5 detik yang menyuplai seluruh beban 616 kVA. Secara keseluruhan, revitalisasi terbukti meningkatkan keandalan, kualitas pasokan, dan ketahanan sistem secara menyeluruh guna mewujudkan kontinuitas pasokan tanpa gangguan (zero interrupted supply) sesuai status VVIP kawasan.
SMA Taruna Nusantara is a VVIP boarding school educational area that demands high reliability and continuity of electrical power supply; therefore, its power distribution system was revitalized from a single-source radial configuration into a dual-feeder system. This Final Project aims to analyze and compare the performance of the area's power distribution system under pre- and post-revitalization conditions through four studies, namely power flow analysis, N-1 contingency, voltage stability based on the P-V curve, and frequency stability, simulated using DIgSILENT PowerFactory 2021 SP2. The power flow analysis results show that both systems comply with the standards, with bus voltages within the range of 0.90–1.05 pu in accordance with SPLN 1:1995. The highest line loading before revitalization was 63.87% on the Trf1–Office line and 62.59% on the Trf1–Balairung line after revitalization, both below the 80% limit in accordance with PLN Director Circular No. 0017.E/DIR/2014. The N-1 contingency analysis demonstrates the tangible impact of revitalization — before revitalization the 400 kVA generator set could only supply the Office Bus when SGN11 tripped, whereas after revitalization the ACOS TR automatically transferred the supply to the 1,000 kVA generator set within 0.5 seconds so that all buses in the area remained supplied with voltages of 0.993–0.999 pu and the highest line loading at 62.26% on the Generator–Balairung line. The voltage stability analysis shows a significant strengthening of voltage resilience in the post-revitalization system, indicated by the increase of the nose point load from 0.93–1.84 MW to 5.49–5.59 MW and the decrease of the loading comparison value (M) from 6.07%–7.36% to below 3%, making the system safer against voltage collapse. The frequency stability analysis reveals that both systems are able to restore the frequency to 50 Hz with nadir values meeting the minimum limit of ? 47.0 Hz in accordance with Minister of Energy and Mineral Resources Regulation No. 20/2020, with a nadir of 49.006 Hz before revitalization through manual transfer of approximately 3 minutes, and 48.45 Hz after revitalization through automatic transfer of 0.5 seconds supplying the entire 616 kVA load. Overall, the revitalization is proven to improve the reliability, supply quality, and system resilience comprehensively in order to achieve uninterrupted power supply (zero interrupted supply) in accordance with the area's VVIP status.
Kata Kunci : aliran daya, DIgSILENT PowerFactory, kontingensi N-1, revitalisasi sistem distribusi,stabilitas frekuensi, stabilitas tegangan