Warning System Kebocoran Pipa dengan Prinsip Differential Pressure menggunakan Sensor MPX5050Dp

Muhammad Haekal Faiq, Dr. Trias Prima Satya, S.Si., M.Sc.

2026 | Tugas Akhir | D4 Teknologi Rekayasa Instrumentasi dan Kontrol

Kebocoran pada sistem jaringan pipa merupakan salah satu penyebab utama kehilangan
fluida dan penurunan efisiensi distribusi pada sektor industri. Penelitian ini bertujuan untuk
menguji keandalan sistem deteksi dini (early warning system) kebocoran pipa berbasis
prinsip tekanan diferensial (?P) menggunakan venturi tube sebagai elemen pembangkit
primer. Sistem ini dikembangkan menggunakan mikrokontroler ESP32 dan sensor
MPX5050DP yang terintegrasi dengan platform IoT Blynk Cloud. Melalui pengujian
prototipe dengan spesifikasi venturi tube berdiameter inlet 22 mm dan throat 6 mm, data
dari sensor upstream dan downstream difilter menggunakan mean filter untuk mereduksi
noise, serta diintegrasikan dengan modul relay untuk automatic shutdown pompa.
Pengujian dilakukan melalui simulasi intensitas kebocoran bertahap, mulai dari kondisi
normal (0%) hingga kebocoran total (100%). Hasil eksperimen menunjukkan hubungan
yang kuat dan proporsional antara peningkatan intensitas kebocoran dengan dinamika
tekanan sistem. Pada kondisi kebocoran kritis (75%), tekanan hulu mengalami kenaikan
rata-rata sebesar 12,71 kPa akibat efek backpressure dan aliran turbulen setempat,
sedangkan tekanan hilir menurun menjadi 2,17 kPa. Analisis statistik melalui regresi linear
tunggal mengonfirmasi bahwa parameter selisih tekanan (?P) memiliki sensitivitas tertinggi
terhadap variasi kebocoran dibandingkan pembacaan sensor individual. Penelitian ini
membuktikan secara empiris bahwa pemantauan parameter ?P berbasis IoT sangat andal
dan responsif untuk diaplikasikan sebagai instrumen diagnostik utama dalam mencegah
risiko kerusakan fatal pada jaringan pipa.

Leakage in piping network systems is one of the primary causes of fluid loss and reduced
distribution efficiency in the industrial sector. This study aims to evaluate the reliability of
an early warning system for pipe leakage detection based on the differential pressure 
(?P)
principle, utilizing a venturi tube as the primary generating element. The system was
developed using an ESP32 microcontroller and an MPX5050DP sensor integrated with the
Blynk Cloud IoT platform. Through prototype testing using a venturi tube with an inlet
diameter of 22 mm and a throat diameter of 6 mm, data from the upstream and downstream
sensors were filtered using a mean filter to reduce noise, and integrated with a relay module
for automatic pump shutdown. Testing was conducted through simulations of gradual leak
intensities, ranging from normal conditions (0%) to total leakage (100%). Experimental
results demonstrated a strong and proportional relationship between increased leak
intensity and system pressure dynamics. Under critical leak conditions (75%), the upstream
pressure experienced an average increase of 12.71 kPa due to backpressure effects and
localized turbulent flow, while the downstream pressure decreased to 2.17 kPa. Statistical
analysis using simple linear regression confirmed that the differential pressure parameter
(
?P) possesses the highest sensitivity to leak variations compared to individual sensor
readings. This study empirically proves that IoT-based monitoring of the 
?P parameter is
highly reliable and responsive for application as a primary diagnostic instrument in
preventing the risk of catastrophic failure in piping networks.


Kata Kunci : Kata kunci: Tekanan Diferensial, Kebocoran Pipa, Internet of Things, MPX5050DP. Sistem Peringatan Dini