Identifikasi Akar Penyebab Gangguan Jaringan Distribusi Tegangan Menengah Menggunakan Fault Tree Analysis (FTA) serta Analisis Energy Not Supplied (ENS) Berdasarkan Data Operasi PMT, Recloser, dan LBS SSO di PT PLN (Persero) UP3 Surakarta
Marshanda Ifany Ashari, Ir. Unan Yusmaniar Oktiawati, S.T., M.Sc., Ph.D., IPU
2026 | Tugas Akhir | D4 TEKNOLOGI REKAYASA ELEKTRO
Gangguan pada jaringan distribusi tegangan menengah dapat menyebabkan terputusnya penyaluran energi listrik kepada pelanggan dan menurunkan keandalan sistem distribusi. Penelitian ini bertujuan untuk menghitung nilai Energy Not Supplied (ENS) dan Average Energy Not Supplied (AENS), menentukan faktor dominan penyebab gangguan, serta mengidentifikasi akar penyebab gangguan menggunakan metode Fault Tree Analysis (FTA) pada jaringan distribusi tegangan menengah PT PLN (Persero) UP3 Surakarta. Data yang digunakan berupa data historis gangguan tahun 2025 yang berasal dari peralatan proteksi Pemutus Tenaga (PMT), Recloser, dan Load Break Switch (LBS) dengan sistem Saklar Seksi Otomatis (SSO) yang tercatat pada sistem Supervisory Control and Data Acquisition (SCADA). Perhitungan ENS dan AENS dilakukan berdasarkan data gangguan dan jumlah pelanggan, sedangkan identifikasi akar penyebab gangguan dilakukan menggunakan metode FTA berdasarkan hasil wawancara dengan pihak PT PLN (Persero) UP3 Surakarta. Hasil penelitian menunjukkan bahwa total ENS pada PT PLN (Persero) UP3 Surakarta tahun 2025 sebesar 5.593.748 kWh dengan nilai AENS sebesar 5,82 kWh/pelanggan/tahun. Faktor dominan penyebab gangguan adalah kategori pohon (E1) dengan jumlah 282 gangguan atau sebesar 29,8?ri total gangguan, diikuti oleh kategori pihak ketiga/binatang (E3) dengan jumlah 234 gangguan atau sebesar 24,7%. Hasil analisis FTA menunjukkan bahwa akar penyebab gangguan berasal dari faktor lingkungan dan kondisi aset jaringan. Faktor lingkungan meliputi vegetasi di sekitar jaringan, aktivitas pihak ketiga, gangguan binatang, dan kondisi cuaca, sedangkan faktor kondisi aset berkaitan dengan umur operasi peralatan serta penurunan kualitas material. Hasil penelitian menunjukkan bahwa faktor penyebab gangguan tersebut berkontribusi terhadap terjadinya gangguan jaringan distribusi dan berdampak pada meningkatnya energi listrik yang tidak tersalurkan kepada pelanggan.
Power outages in medium voltage distribution networks can interrupt electricity supply to customers and reduce the reliability of the distribution system. This study aims to calculate the Energy Not Supplied (ENS) and Average Energy Not Supplied (AENS), determine the dominant factors causing disturbances, and identify the root causes of disturbances using the Fault Tree Analysis (FTA) method in the medium voltage distribution network of PT PLN (Persero) UP3 Surakarta. The data used in this study are historical disturbance data in 2025 obtained from protection equipment, including Circuit Breaker (CB), Recloser, and Load Break Switch (LBS) with an Automatic Sectionalizer System (SSO) recorded in the Supervisory Control and Data Acquisition (SCADA) system. ENS and AENS calculations were performed based on disturbance data and the number of customers, while the identification of root causes was carried out using the FTA method based on interviews with PT PLN (Persero) UP3 Surakarta personnel. The results showed that the total ENS of PT PLN (Persero) UP3 Surakarta in 2025 was 5,593,748 kWh, with an AENS value of 5.82 kWh/customer/year. The dominant cause of disturbances was the tree category (E1), with 282 incidents or 29.8% of the total disturbances, followed by the third party/animal category (E3), with 234 incidents or 24.7%. The FTA analysis showed that the root causes of disturbances originated from environmental factors and network asset conditions. Environmental factors included vegetation around the network, third-party activities, animal disturbances, and weather conditions, while asset condition factors were related to equipment operating age and material degradation. The results indicate that these factors contribute to the occurrence of distribution network disturbances and affect the increase in unserved electrical energy supplied to customers.
Kata Kunci : gangguan jaringan distribusi, ENS, AENS, Fault Tree Analysis (FTA), keandalan sistem distribusi.