Analisis Ketahanan Side Flash pada Berbagai Jenis Down Conductor terhadap Variasi Separation Distance dan Tegangan Impuls
Septo Mellandri, Mochammad Wahyudi, S.T., M.T. ; Prof. Ir. Tumiran, M. Eng., Ph. D., IPU.
2026 | Skripsi | TEKNIK ELEKTRO
Petir merupakan salah satu sumber gangguan transien yang dapat menyebabkan kerusakan pada bangunan, sistem tenaga listrik, dan peralatan elektronik. Salah satu komponen penting dalam sistem proteksi petir eksternal adalah down conductor yang berfungsi menyalurkan arus petir ke sistem pentanahan. Penelitian ini bertujuan menganalisis ketahanan side flash pada berbagai jenis down conductor terhadap variasi separation distance dan tegangan impuls.
Pengujian dilakukan di Laboratorium Teknik Tegangan Tinggi DTETI FT UGM menggunakan pembangkit tegangan impuls 200 kV Ogawa Seiki dan 1200 kV Passoni Villa. Variasi separation distance terhadap elektroda pentanahan digunakan untuk memperoleh tegangan tembus dan mengamati fenomena pelepasan listrik. Data direkam menggunakan osiloskop dan kamera, kemudian diolah menggunakan Python.
Hasil pengujian menunjukkan bahwa semakin besar separation distance, semakin tinggi tegangan yang diperlukan untuk memicu pelepasan listrik. Pada separation distance 5 cm, bare conductor berlapis PVC menghasilkan tegangan tembus tertinggi sebesar 128,63 kV, diikuti insulated down conductor sebesar 107,63 kV dan bare conductor sebesar 102,88 kV. Pada pengujian tegangan impuls 250 kV, jarak maksimum terjadinya pelepasan listrik berturut-turut adalah 28 cm, 26 cm, dan 27 cm untuk bare conductor berlapis PVC, insulated down conductor, dan bare conductor.
Hasil penelitian menunjukkan bahwa keberadaan lapisan isolasi memengaruhi karakteristik tegangan tembus dan jarak pelepasan listrik pada kondisi tegangan impuls. Penelitian ini diharapkan dapat menjadi referensi dalam pemilihan down conductor untuk meningkatkan keandalan sistem proteksi petir.
Lightning is a source of transient disturbances that can cause damage to buildings, electrical power systems, and electronic equipment. A critical component of an external lightning protection system is the down conductor, which channels the lightning current to the grounding system. This study aims to analyze the side flash resistance of various types of down conductors against variations in separation distance and impulse voltage.
Tests were conducted in the High Voltage Engineering Laboratory of the Faculty of Engineering, Gadjah Mada University (UGM) using a 200 kV Ogawa Seiki and 1200 kV Passoni Villa impulse voltage generator. Variations in separation distance from the ground electrode were used to obtain breakdown voltages and observe electrical discharge phenomena. Data were recorded using an oscilloscope and camera, then processed using Python.
Test results showed that the greater the separation distance, the higher the voltage required to trigger an electrical discharge. At a separation distance of 5 cm, the PVC-coated bare conductor produced the highest breakdown voltage of 128.63 kV, followed by the insulated down conductor at 107.63 kV and the bare conductor at 102.88 kV. In the 250 kV impulse voltage test, the maximum distances for electrical discharge were 28 cm, 26 cm, and 27 cm for the PVC-coated bare conductor, the insulated down conductor, and the bare conductor, respectively.
The results show that the presence of an insulating layer affects the breakdown voltage characteristics and electrical discharge distance under impulse voltage conditions. This research is expected to serve as a reference in selecting down conductors to improve the reliability of lightning protection systems.
Kata Kunci : sistem proteksi petir, down conductor, tegangan impuls, tegangan tembus, isolasi.