Pemodelan dan Analisis Proteksi Over-Flux Transformator Berbasis Rangkaian RC-Seri dan Karakteristik Relay IDMT
Dalilul Falihin, Dr. Ir. Mokhammad Isnaeni B.S., M.T. ; Husni Rois Ali, S.T., M.Eng., Ph.D., DIC., SMIEEE.
2026 | Skripsi | TEKNIK ELEKTRO
Kondisi over-fluxing pada transformator
terjadi ketika rasio tegangan terhadap frekuensi atau V/f meningkat melebihi
kondisi nominal, sehingga dapat menyebabkan saturasi inti, peningkatan
rugi-rugi, pemanasan lokal, penurunan kualitas isolasi, hingga risiko kegagalan
transformator. Penelitian ini bertujuan untuk menganalisis sistem proteksi
over-flux transformator menggunakan pendekatan rangkaian RC-seri yang diintegrasikan dengan relay IDMT dan circuit breaker. Penelitian dilakukan melalui
simulasi MATLAB/Simulink dan analisis respons frekuensi LTspice. Sistem yang
dimodelkan terdiri atas sumber tiga fasa, transformator, beban impedansi
konstan, potential transformer, rangkaian pendeteksi RC-seri, relay IDMT, dan
circuit breaker. Tegangan kapasitor rangkaian RC-seri digunakan sebagai sinyal
deteksi yang dinormalisasi terhadap kondisi nominal untuk memperoleh nilai
pengali over-flux atau OF.
Hasil simulasi menunjukkan bahwa tegangan
kapasitor nominal sebesar 3,5V dapat digunakan sebagai acuan pembentukan nilai
OF. Rangkaian RC-seri mampu menunjukkan peningkatan nilai OF ketika tegangan
dinaikkan atau frekuensi diturunkan. Pada pengujian kombinasi, saat tegangan
dinaikkan menjadi 96,64kV dan frekuensi di turunkan menjadi 40Hz, nilai OF
teoritis mencapai 1,5851 dan nilai OF simulasi sensor mencapai 1,5928. Sensor
memiliki jeda transien sekitar 0,6s sebelum mendekati kondisi stabil. Relay IDMT
dengan parameter k = 3 dan d = 0,8s menghasilkan karakteristik waktu kerja
invers; pada nilai OF simulasi 1,5783, waktu trip menjadi 2,4800 s. Pada salah
satu skenario, gangguan terjadi pada t = 1s dengan OF sekitar 1,4118 pu dan
perintah trip muncul sekitar t = 4,92s.
Berdasarkan hasil tersebut, metode RC-seri
dapat digunakan sebagai pendekatan sederhana untuk mendeteksi peningkatan rasio
V/f pada kondisi over-fluxing. Integrasi rangkaian pendeteksi, relay IDMT, dan
circuit breaker mampu merespons gangguan secara terkoordinasi sesuai tingkat
keparahan nilai OF. Namun, kinerja metode ini masih dipengaruhi oleh pemilihan
parameter R dan C, proses pembacaan RMS, kondisi transien sensor, serta
langkah waktu simulasi, sehingga validasi perangkat keras dan optimasi parameter
masih diperlukan untuk pengembangan selanjutnya.
Transformer over-fluxing occurs when the
voltage-to-frequency ratio, or V/f, exceeds its nominal condition, which may
cause core saturation, increase losses, local heating, insulation degradation,
and transformer failure risk. This research analyzes a transformer over-flux
protection system using a series RC circuit integrated with an IDMT relay and a
circuit breaker. The study was conducted through MATLAB/Simulink simulation and
LTspice frequency-response analysis. The modeled system consists of a three-phase
source, transformer, constant impedance load, potential transformer, series RC
detection circuit, IDMT relay, and circuit breaker. The capacitor voltage of
the series RC circuit is used as a detection signal and normalized against the
nominal condition to obtain the over-flux variable, OF.
The simulation results show that the nominal
capacitor voltage of 3.5V can be used as a reference to form OF. The series RC
circuit indicates an increase in OF when the voltage is increased or the
frequency is decreased. In the combined test, when the voltage was increased to
96.64kV and the frequency was reduced to 40Hz, the theore tical OF reached
1.5851, while the simulated sensor value reached 1.5928. The sensor had a
transient delay of approximately 0.6s before approaching steady state. The IDMT
relay with parameters k = 3 and d = 0.8s produced an inverse operating-time
characte ristic; at a simulated OF value of 1.5783, the trip time was 2.4800 s.
In one disturbance scenario, the disturbance occurred at t = 1s with OF
approximately 1.4118 pu, and the trip command appeared at approximately t =
4.92s.
Based on these results, the series RC method
can be used as a simple approach to detect an increase in the V/f ratio during
over-fluxing conditions. The integration of the detection circuit, IDMT relay,
and circuit breaker responds to disturbances in a coordinated manner according
to the severity of OF. However, the method performan ce is still affected by
the selection of R and C parameters, RMS measurement process, sensor transient
response, and simulation time step; therefore, hardware validation and parameter
optimization are required for further development.
Kata Kunci : over-fluxing, transformator, rangkaian RC-seri, relay IDMT, rasio V/f