Pemodelan dan Analisis Proteksi Over-Flux Transformator Berbasis Rangkaian RC-Seri dan Karakteristik Relay IDMT

Dalilul Falihin, Dr. Ir. Mokhammad Isnaeni B.S., M.T. ; Husni Rois Ali, S.T., M.Eng., Ph.D., DIC., SMIEEE.

2026 | Skripsi | TEKNIK ELEKTRO

Kondisi over-fluxing pada transformator terjadi ketika rasio tegangan terhadap frekuensi atau V/f meningkat melebihi kondisi nominal, sehingga dapat menyebabkan saturasi inti, peningkatan rugi-rugi, pemanasan lokal, penurunan kualitas isolasi, hingga risiko kegagalan transformator. Penelitian ini bertujuan untuk menganalisis sistem proteksi over-flux transformator menggunakan pendekatan rangkaian RC-seri yang diintegrasikan dengan relay IDMT dan circuit breaker. Penelitian dilakukan melalui simulasi MATLAB/Simulink dan analisis respons frekuensi LTspice. Sistem yang dimodelkan terdiri atas sumber tiga fasa, transformator, beban impedansi konstan, potential transformer, rangkaian pendeteksi RC-seri, relay IDMT, dan circuit breaker. Tegangan kapasitor rangkaian RC-seri digunakan sebagai sinyal deteksi yang dinormalisasi terhadap kondisi nominal untuk memperoleh nilai pengali over-flux atau OF.

Hasil simulasi menunjukkan bahwa tegangan kapasitor nominal sebesar 3,5V dapat digunakan sebagai acuan pembentukan nilai OF. Rangkaian RC-seri mampu menunjukkan peningkatan nilai OF ketika tegangan dinaikkan atau frekuensi diturunkan. Pada pengujian kombinasi, saat tegangan dinaikkan menjadi 96,64kV dan frekuensi di turunkan menjadi 40Hz, nilai OF teoritis mencapai 1,5851 dan nilai OF simulasi sensor mencapai 1,5928. Sensor memiliki jeda transien sekitar 0,6s sebelum mendekati kondisi stabil. Relay IDMT dengan parameter k = 3 dan d = 0,8s menghasilkan karakteristik waktu kerja invers; pada nilai OF simulasi 1,5783, waktu trip menjadi 2,4800 s. Pada salah satu skenario, gangguan terjadi pada t = 1s dengan OF sekitar 1,4118 pu dan perintah trip muncul sekitar t = 4,92s.

Berdasarkan hasil tersebut, metode RC-seri dapat digunakan sebagai pendekatan sederhana untuk mendeteksi peningkatan rasio V/f pada kondisi over-fluxing. Integrasi rangkaian pendeteksi, relay IDMT, dan circuit breaker mampu merespons gangguan secara terkoordinasi sesuai tingkat keparahan nilai OF. Namun, kinerja metode ini masih dipengaruhi oleh pemilihan parameter R dan C, proses pembacaan RMS, kondisi transien sensor, serta langkah waktu simulasi, sehingga validasi perangkat keras dan optimasi parameter masih diperlukan untuk pengembangan selanjutnya.

Transformer over-fluxing occurs when the voltage-to-frequency ratio, or V/f, exceeds its nominal condition, which may cause core saturation, increase losses, local heating, insulation degradation, and transformer failure risk. This research analyzes a transformer over-flux protection system using a series RC circuit integrated with an IDMT relay and a circuit breaker. The study was conducted through MATLAB/Simulink simulation and LTspice frequency-response analysis. The modeled system consists of a three-phase source, transformer, constant impedance load, potential transformer, series RC detection circuit, IDMT relay, and circuit breaker. The capacitor voltage of the series RC circuit is used as a detection signal and normalized against the nominal condition to obtain the over-flux variable, OF.

The simulation results show that the nominal capacitor voltage of 3.5V can be used as a reference to form OF. The series RC circuit indicates an increase in OF when the voltage is increased or the frequency is decreased. In the combined test, when the voltage was increased to 96.64kV and the frequency was reduced to 40Hz, the theore tical OF reached 1.5851, while the simulated sensor value reached 1.5928. The sensor had a transient delay of approximately 0.6s before approaching steady state. The IDMT relay with parameters k = 3 and d = 0.8s produced an inverse operating-time characte ristic; at a simulated OF value of 1.5783, the trip time was 2.4800 s. In one disturbance scenario, the disturbance occurred at t = 1s with OF approximately 1.4118 pu, and the trip command appeared at approximately t = 4.92s.

Based on these results, the series RC method can be used as a simple approach to detect an increase in the V/f ratio during over-fluxing conditions. The integration of the detection circuit, IDMT relay, and circuit breaker responds to disturbances in a coordinated manner according to the severity of OF. However, the method performan ce is still affected by the selection of R and C parameters, RMS measurement process, sensor transient response, and simulation time step; therefore, hardware validation and parameter optimization are required for further development.

Kata Kunci : over-fluxing, transformator, rangkaian RC-seri, relay IDMT, rasio V/f