Perancangan dan Pengujian Inverter Grid-Following Menggunakan Platform Simulasi Thyphoon HIL
Nurhalizah Salzabila Tappi, Prof. Dr.Eng. Ir. F. Danang Wijaya, S.T., M.T., IPM.; Husni Rois Ali, S.T., M.Eng., Ph.D., DIC., SMIEEE.
2026 | Skripsi | TEKNIK ELEKTRO
Transisi energi nasional menuju sistem terbarukan menuntut integrasi Inverter-Based Resources (IBR) secara masif. Perancangan dan pengujian stabilitas inverter grid-following (GFL) menjadi sangat krusial dalam sistem kelistrikan berinersia rendah. Penelitian ini mendesain algoritma kontrol cascaded pada kerangka dq untuk inverter GFL 5 kVA. Implementasi kontrol ini dimodelkan menggunakan platform simulasi Typhoon HIL. Validasi sistem dilakukan secara bertahap melalui simulasi Virtual-HIL (V-HIL) dan eksekusi real-time pada Controller-HIL (C-HIL). Pengujian C-HIL menggunakan simulator Typhoon HIL604 dengan integrasi mikrokontroler TI F28069M. Skenario evaluasi mencakup respons kondisi steady state dan dinamika injeksi daya aktif-reaktif. Ketahanan Phase-Locked Loop (PLL) juga diuji terhadap Voltage Unbalance Factor (VUF) hingga 10%.
Hasil pengujian menunjukkan kontroler mampu mempertahankan stabilitas arus injeksi. Kontroler mampu melacak referensi daya secara indepeenden dengan respons transien presisi pada berbagai kondisi operasi. Dari sisi komparasi, V-HIL terbukti menjadi metode validasi awal yang sangat selaras dengan C-HIL pada kondisi normal. Namun simulasi virtual belum sepenuhnya menangkap tekanan komputasi perangkat keras saat menghadapi gangguan asimetris ekstrem. Gangguan ekstrem ini secara nyata memicu ketidakstabilan algoritma sinkronisasi standar pada pengujian C-HIL. Hasil pengujian ketahanan menunjukkan bahwa metode SRF-PLL mengalami kegagalan sinkronisasi mulai dari tingkat gangguan VUF 5%. Lebih lanjut, DSRF-PLL diimplementasikan untuk mengatasi temuan masalah tersebut. Implementasi ini terbukti sukses mengisolasi komponen tegangan urutan negatif dan mampu bertahan menghadapi gangguan ketidakseimbangan ekstrem hingga tingkat VUF 10%.
The national energy transition toward renewable systems demands the massive integration of Inverter-Based Resources (IBR). Designing and testing the stability of grid-following (GFL) inverters becomes highly crucial in low-inertia power systems. This study designs a cascaded control algorithm on the dq frame for a 5 kVA GFL inverter. The implementation of this control is modeled using the Typhoon HIL simulation platform. System validation is performed progressively through Virtual-HIL (V-HIL) simulation and real-time execution on Controller-HIL (C-HIL). The C-HIL testing utilizes a Typhoon HIL604 simulator with the integration of a TI F28069M microcontroller. The evaluation scenarios encompass steady-state responses and active-reactive power injection dynamics. The resilience of the Phase-Locked Loop (PLL) is also tested against a Voltage Unbalance Factor (VUF) up to 10%.
The experimental results demonstrate that the controller is capable of maintaining the stability of the injected current. The controller can independently track power references with precise transient responses under various operating conditions. In terms of comparison, V-HIL is proven to be an initial validation method that aligns well with C-HIL under normal conditions. However, the virtual simulation fails to fully capture the hardware computational stress when facing extreme asymmetrical disturbances. These extreme disturbances significantly trigger instability in the standard synchronization algorithm during C-HIL testing. The robustness test results indicate that the SRF-PLL method experiences synchronization failure starting from a VUF of 5%. Furthermore, DSRF-PLL was implemented to address this identified issue. This implementation is proven successful in isolating negative-sequence voltage components and is capable of withstanding extreme unbalance disturbances up to a 10% VUF level.
Kata Kunci : Inverter Grid-Following, C-HIL, V-HIL, Phase-Locked Loop, Grid Unbalance