Evaluasi Setting Relay SEL-749M Sebagai Proteksi Motor Induksi 33P1BM di Substation 30SS1 Area Oil Movement PT Kilang Pertamina Internasional RU IV Cilacap
G.Arya Kusna Sakti, Ir. Muhammad Arrofiq, S.T., M.T., Ph.D., IPM
2026 | Tugas Akhir | D4 TEKNOLOGI REKAYASA ELEKTRO
Motor induksi 33P1BM berkapasitas 1500 HP merupakan salah satu aset
penggerak kritikal di area kilang yang membutuhkan sistem proteksi dengan tingkat
keandalan dan selektivitas tinggi. Penelitian ini bertujuan untuk mengevaluasi
kinerja dan kelayakan konfigurasi setting proteksi eksisting pada Relay SEL-749M.
Metode penelitian dilakukan secara komparatif melalui pengujian injeksi fisik
menggunakan alat uji Secondary Current Injector (FREJA 300) dan validasi teoretis
melalui pemodelan kurva Time-Current Characteristic (TCC) menggunakan
perangkat lunak ETAP 19.0.1. Evaluasi difokuskan pada pengujian lima elemen
proteksi utama, yaitu Over Load, Phase Unbalance, Lock Rotor Trip, Mechanical Jam,
dan Ground Fault. Kondisi setting pada masing-masing elemen ditinjau berdasarkan
kesesuaiannya dengan spesifikasi nominal motor dan batas toleransi standar termal.
Sementara itu, perolehan hasil evaluasi didapatkan dengan menyandingkan serta
menghitung deviasi waktu pemutusan (trip time) antara eksekusi instrumen keras
aktual di lapangan terhadap waktu kalkulasi teoretis pada kurva simulasi.
Hasil pengujian menunjukkan bahwa relay beroperasi dengan tingkat akurasi
tinggi pada perlindungan berbasis kurva termal dengan persentase error di bawah
2%. Pada elemen transien mekanis, deviasi waktu aktual berada pada rentang aman
30-40 milidetik.
Selain itu, ditemukan adanya limitasi masukan waktu tunda
minimum sebesar 0,100 detik pada software ETAP saat memodelkan gangguan ke
tanah (Ground Fault), sedangkan instrumen keras aktual terbukti jauh lebih superior
dengan mengeksekusi trip seketika dalam waktu 45 milidetik. Secara keseluruhan,
kinerja proteksi relay SEL-749M terbukti masih dalam kondisi sangat prima, selektif,
dan sepenuhnya laik operasi untuk melindungi motor dari ancaman kerusakan fatal.
The 1500 HP 33P1BM induction motor is a critical prime mover asset in the
refinery area that requires a highly reliable and selective protection system. This
research aims to evaluate the performance and feasibility of the existing protection
settings configured on the SEL-749M Relay
The research methodology was conducted comparatively through physical
injection testing using a Secondary Current Injector instrument (FREJA 300) and
theoretical validation through Time-Current Characteristic (TCC) curve modeling
using ETAP 19.0.1 software. The evaluation focused on five main protection
elements: Over Load, Phase Unbalance, Lock Rotor Trip, Mechanical Jam, and
Ground Fault. The setting conditions for each element were reviewed based on their
compliance with the motor’s nominal specifications and thermal standard tolerance
limits. Meanwhile, the evaluation results were obtained by comparing and calculating
the tripping time deviation between the execution of the actual hardware instrument
in the field and the theoretical calculation time on the simulation curve.
The testing results showed that the relay operates with high accuracy on thermal
curve-based protection, with an error percentage of under 2%. In mechanical transient
elements, the actual time deviation is within the safe range of 30-40 milliseconds.
Furthermore, a minimum time delay limitation of 0.100 seconds was found in the
ETAP software when modeling Ground Faults, whereas the actual hardware instrument
proved to be far superior by executing instantaneous trips in 45 milliseconds. Overall,
the protection performance of the SEL-749M relay is proven to be in prime condition,
selective, and entirely fit for operation to protect the motor from catastrophic failure
threats.
Kata Kunci : Kata kunci: ETAP, FREJA 300, Motor Induksi, Relay Proteksi, SEL-749M, Waktu Pemutusan/Key words: ETAP, FREJA 300, Induction Motor, Protection Relay, SEL-749M, Tripping Time.