Analisis Deteksi High Impedance Fault Berbasis Hilbert Transform dan Pemodelan Impedansi Statis pada Sistem IEEE 39-BUS
Hansen Justin Handijaya, M. Isnaeni Bambang Setyonegoro, Dr. Ir., M.T. ; Rian Fatah Mochamad, S.T., M.Eng., Ph.D.
2026 | Skripsi | TEKNIK ELEKTRO
Gangguan tanah berimpedansi tinggi atau High Impedance Fault (HIF) merupakan salah satu jenis gangguan pada sistem tenaga listrik yang sulit dideteksi oleh proteksi konvensional karena arus gangguannya relatif kecil dan karakteristik sinyalnya dapat menyerupai kondisi transien non-gangguan. Penelitian ini bertujuan untuk menganalisis performa metode deteksi gangguan berbasis Hilbert Transform dan instantaneous frequency dalam mendeteksi HIF serta mengevaluasi kemampuannya pada beberapa scenario gangguan dan non-gangguan.
Penelitian dilakukan dengan memodelkan sistem IEEE 39-bus pada DIgSILENT PowerFactory. Data arus tiga fasa hasil simulasi diekspor dalam format .csv dan diproses menggunakan MATLAB. Tahapan pengolahan sinyal meliputi perhitungan RMS dengan moving window, pembentukan sinyal analitik menggunakan Hilbert Transform, perhitungan instantaneous frequency, pembentukan Detection Index (DI), serta penerapan trip logic dengan nilai dasar ambang K = 0,5. Skenario pengujian meliputi HIF, Low Impedance Fault (LIF), reverse fault, capacitor bank switching, dan pengaruh White Gaussian Noise (WGN).
Hasil pengujian menunjukkan bahwa metode yang digunakan mampu mendeteksi HIF pada sistem IEEE 39-bus. Pada gangguan HIF satu fasa ke tanah dengan R = 500 ? dan X=50?,metode menghasilkan sinyal trip hanya pada fasa A dengan waktu deteksi 83,3 ms. Pada kasus R = 1000 ? dan X = 100?, metode tetap mampu mendeteksi fasa terganggu dengan waktu deteksi 83,3 ms. Untuk gangguan HIF tiga fasa, metode menghasilkan sinyal trip pada ketiga fasa dengan waktu deteksi 63,5 ms dan 69,5 ms untuk dua variasi impedansi yang diuji. Pada pengujian LIF, metode mampu mendeteksi gangguan tiga fasa dalam 85,7 ms dan gangguan satu fasa ke tanah dalam 97,3 ms, meskipun masih terdapat keterbatasan selektivitas fasa pada kasus LIF satu fasa. Metode juga tidak menghasilkan false trip pada skenario capacitor bank switching dan tetap bekerja pada sinyal berderau. Dengan demikian, metode berbasis Hilbert Transform dan instantaneous frequency berpotensi digunakan sebagai pendekatan deteksi gangguan yang sensitif terhadap HIF, selektif terhadap transien non-gangguan, dan cukup robust terhadap variasi kondisi pengujian.
High Impedance Fault (HIF) is one of the most difficult faults to detect in power systems because its fault current is relatively low and its signal characteristics may resemble non-fault transient events. This research aims to analyze the performance of a fault detection method based on the Hilbert Transform and instantaneous frequency for detecting HIF and evaluating its performance under several fault and non-fault scenarios.
The study was conducted by modeling the IEEE 39-bus system in DIgSILENT PowerFactory. The three-phase current data obtained from the simulations were exported in .csv format and processed using MATLAB. The signal processing stages include RMS calculation using a moving window, analytic signal construction using the Hilbert Transform, instantaneous frequency calculation, Detection Index (DI) formation, and trip logic implementation with a base threshold value of K = 0.5. The tested scenarios include HIF, Low Impedance Fault (LIF), reverse fault, capacitor bank switching, and White Gaussian Noise (WGN).
The results show that the proposed method is capable of detecting HIF in the IEEE 39-bus system. For a single-line-to-ground HIF with R = 500 ? and X = 50 ?, the method generates a trip signal only on phase A with a detection time of 83.3 ms. For R = 1000 ? and X = 100 ?, the method is still able to identify the faulted phase with a detection time of 83.3 ms. For three-phase HIF cases, the method generates trip signals on all three phases with detection times of 63.5 ms and 69.5 ms for the two tested impedance variations. In LIF testing, the method detects a three-phase fault in 85.7 ms and a single-line-to-ground fault in 97.3 ms, although phase selectivity remains limited in the single-phase LIF case. The method also avoids false trips during capacitor bank switching and remains effective under noisy signal conditions. Therefore, the Hilbert Transform and instantaneous-frequency-based method has the potential to be used as a fault detection approach that is sensitive to HIF, selective against non-fault transients, and sufficiently robust under various testing conditions.
Kata Kunci : High Impedance Fault, Hilbert Transform, Instantaneous Frequency, Detection-Index, Proteksi Sistem Tenaga Listrik