Laporkan Masalah

Perancangan dan Analisis Sistem Mikrogrid DC 48 V untuk Aplikasi Shelter Evakuasi Bencana dengan Cascaded V–I Droop Control

Adi Wicaksana, Prof. Dr.Eng. Ir. F. Danang Wijaya, S.T., M.T., IPM. ; Dr.-Ing. Ir. Yohan Fajar Sidik, S.T., M.Eng.

2026 | Skripsi | TEKNIK ELEKTRO

Ketersediaan pasokan daya listrik yang andal pada fasilitas darurat seperti shelter evakuasi bencana merupakan kebutuhan vital, terutama ketika jaringan listrik utama mengalami kelumpuhan. Penelitian ini bertujuan merancang dan menganalisis kinerja sistem mikrogrid DC mandiri (islanded) berkapasitas 1.500 W dengan tegangan bus nominal 48 V untuk menjamin kontinuitas suplai daya beban kritis. Arsitektur sistem mengintegrasikan sumber DC sebagai penyuplai daya utama dan baterai sebagai penyangga energi. Strategi manajemen energi diterapkan melalui skema kontrol terdesentralisasi tanpa komunikasi, di mana sumber DC dikonfigurasi menggunakan kontrol arus (current control) dengan injeksi konstan, sementara unit baterai menggunakan kontrol tegangan bertingkat (cascaded voltage-current control) berbasis droop.

Hasil simulasi menunjukkan bahwa strategi yang diusulkan mampu mengatur pembagian daya dan menjaga stabilitas tegangan secara otomatis dalam berbagai kondisi operasi. Pada kondisi nominal, tegangan bus DC teregulasi stabil pada rentang 47 V hingga 48,2 V. Sistem juga terbukti tangguh (robust) saat menghadapi defisit daya dan lonjakan beban ekstrem hingga 1.900 W (26% di atas kapasitas nominal), dengan tegangan terendah tertahan pada 45,6 V yang masih berada dalam batas aman standar ±5%. Transisi mode operasi antara pengisian (charging) dan pengosongan (discharging) baterai berlangsung mulus tanpa overshoot yang signifikan, memvalidasi kelayakan desain ini sebagai solusi infrastruktur kelistrikan darurat yang andal dan efisien.

Reliable power supply availability in emergency facilities such as disaster evacuation shelters is a vital necessity, particularly when the main utility grid is paralyzed. This study aims to design and analyze the performance of an islanded DC microgrid system with a capacity of 1,500 W and a nominal bus voltage of 48 V to ensure power continuity for critical loads. The system architecture integrates a DC source as the main power supplier and a battery as an energy buffer. An energy management strategy is implemented through a decentralized control scheme without communication, where the DC source is configured using current control with constant injection, while the battery unit employs a droop-based cascaded voltage-current control.

Simulation results demonstrate that the proposed strategy is capable of regulating power sharing and maintaining voltage stability automatically under various operating conditions. Under nominal conditions, the DC bus voltage is stably regulated within the range of 47 V to 48.2 V. The system also proves to be robust when facing power deficits and extreme load surges up to 1,900 W (26?ove nominal capacity), with the lowest voltage sustained at 45.6 V, which remains within the safe standard limit of ±5%. The operational mode transition between battery charging and discharging occurs smoothly without significant overshoot, validating the feasibility of this design as a reliable and efficient emergency electrical infrastructure solution.

Kata Kunci : DC Microgrid, Disaster Shelter, Droop Control, Energy Management, DCDC Converter

  1. S1-2026-479036-abstract.pdf  
  2. S1-2026-479036-bibliography.pdf  
  3. S1-2026-479036-tableofcontent.pdf  
  4. S1-2026-479036-title.pdf