BASIC DESIGN PENCAHAYAAN PADA RUANG KHUSUS, BANGUNAN RUMAH SAKIT ”X” MENGGUNAKAN DIALUX EVO

Fachrizal Zulfana Fashih, Ir. Ma’un Budiyanto, S.T., M.T., IPU.

2026 | Tugas Akhir | D4 TEKNOLOGI REKAYASA ELEKTRO

Rumah sakit memiliki berbagai ruang khusus dengan kebutuhan pencahayaan yang berbeda sesuai fungsi dan aktivitasnya. Oleh karena itu, perancangan sistem pencahayaan yang memenuhi standar menjadi penting untuk mendukung kenyamanan visual, keselamatan kerja tenaga medis, serta kualitas pelayanan kesehatan. Penelitian ini bertujuan untuk merancang basic design sistem pencahayaan pada ruang khusus Rumah Sakit “X” menggunakan perangkat lunak DIALux Evo. Perancangan dilakukan pada enam unit, yaitu Instalasi Gawat Darurat (IGD), Radiologi, VK Perina, Intensive Care Unit (ICU), Instalasi Bedah Sentral (IBS), dan Catheterization Laboratory (Cathlab), yang meliputi pemilihan luminer, perhitungan awal jumlah luminer, pemodelan tiga dimensi ruangan, serta penempatan luminer. Target perancangan mengacu pada standar SNI 6197:2020, Permenkes Nomor 40 Tahun 2022, EN 12464-1, dan ANSI/IES RP-29-06. Model hasil perancangan kemudian disimulasikan dan dievaluasi menggunakan parameter iluminansi rata-rata (Em), keseragaman pencahayaan (U0), dan Lighting Power Density (LPD). Hasil simulasi menunjukkan bahwa dari 160 ruangan yang dirancang, sebanyak 146 ruangan (91,3%) telah memenuhi standar, sedangkan 14 ruangan (8,7%) belum memenuhi standar karena nilai U0 berada di bawah batas minimum meskipun nilai Em telah memenuhi target. Selain itu, seluruh unit menghasilkan nilai LPD pada rentang 4,52–6,64 W/m2 , lebih rendah daripada batas maksimum SNI 6197:2020 sebesar 10,33 W/m2 . Hasil analisis menunjukkan bahwa ketidaksesuaian tersebut disebabkan oleh pola distribusi cahaya yang belum optimal terhadap karakteristik geometri ruangan dan dapat diperbaiki melalui penyesuaian tata letak serta konfigurasi luminer. Berdasarkan hasil tersebut, dapat disimpulkan bahwa basic design sistem pencahayaan yang dirancang telah memenuhi standar kualitas pencahayaan dan efisiensi energi pada sebagian besar ruang khusus Rumah Sakit “X”, sehingga dapat dijadikan acuan dalam pengembangan desain pencahayaan pada tahap selanjutnya.
Kata kunci: Pencahayaan Rumah Sakit, DIALux Evo, Iluminansi, Keseragaman Pencahayaan, Lighting Power Density

Hospitals consist of various specialized rooms, each with distinct lighting requirements depending on its function and activities. The design of a standards compliant lighting system is therefore essential to support visual comfort, occupational safety for medical personnel, and the overall quality of healthcare services. This study aims to develop a basic lighting design for specialized rooms at Hospital ”X” using DIALux Evo software, covering six units: the Emergency Department (ED), Radiology, Delivery Room and Neonatology (VK Perina), Intensive Care Unit (ICU), Central Surgical Installation (IBS), and Catheterization Laboratory (Cathlab). The design process included luminaire selection, preliminary calculation of luminaire quantity, three-dimensional room modeling, and luminaire placement, based on target illuminance levels derived from SNI 6197:2020, Indonesian Ministry of Health Regulation No. 40 of 2022, EN 12464-1, and ANSI/IES RP-29-06. The resulting design was simulated and evaluated using average illuminance (Em), illuminance uniformity (Uo), and Lighting Power Density (LPD) parameters. The simulation results show that out of 160 designed rooms, 146 rooms (91.3%) met the established standards, while 14 rooms (8.7%) did not, primarily due to Uo values falling below the minimum threshold despite Em values having been achieved. All units produced LPD values ranging from 4.52 to 6.64 W/m², well below the maximum threshold of 10.33 W/m² set by SNI 6197:2020. Further analysis indicates that the non-compliance was caused by suboptimal light distribution relative to each room’s geometric characteristics, which can be addressed through adjustments to luminaire layout and configuration. Based on these findings, it can be concluded that the lighting basic design produced for the specialized rooms of Hospital ”X” generally complies with applicable lighting quality standards while remaining energy efficient, and may therefore serve as a reference for further design development prior to construction.

Kata Kunci : Pencahayaan Rumah Sakit, DIALux Evo, Iluminansi, Keseragaman Pencahayaan, Lighting Power Density

  1. D4-2026-494547-abstract.pdf  
  2. D4-2026-494547-bibliography.pdf  
  3. D4-2026-494547-tableofcontent.pdf  
  4. D4-2026-494547-title.pdf