Evaluasi Kinerja dan Penentuan Sudut Kemiringan Optimum PLTS On-grid 50 kWp Melalui Simulasi dan Observasi Eksperimental Pada Iklim Tropis (Studi Kasus: UPDL Makassar)
HENDRA BUDIONO PUTRA P, Dr. Ir. Rachmawan Budiarto, S.T., M.T., IPU ; Dr.Eng. Ir. Mohammad Kholid Ridwan, ST, M.Sc., IPU
2026 | Tesis | MAGISTER TEKNIK FISIKA
Implementasi Pembangkit Listrik Tenaga Surya (PLTS) di wilayah tropis
menghadapi tantangan fluktuasi mikroklimat dan temperatur operasional modul
yang tinggi yang dapat menurunkan efisiensi sel surya. Penelitian ini bertujuan
menganalisis pengaruh iklim tropis terhadap kinerja PLTS, memodelkan sistem
PLTS on-grid 50 kWp di UPDL Makassar menggunakan PVsyst, serta
mengevaluasi konsistensi tren performa melalui unit eksperimental guna
menentukan sudut kemiringan tetap (fixed tilt) optimum untuk
meningkatkan produksi energi.
Metodologi penelitian menggunakan pendekatan kuantitatif dengan metode
eksperimental-simulatif. Kinerja sistem utama 50 kWp dievaluasi menggunakan
data historis 2021 dan data verifikasi temporal 2025 saat kondisi de-rating
kapasitas. Secara simultan, sebuah unit eksperimental 1 kWp digunakan untuk
mengamati tren performa relatif pada variasi sudut kemiringan 5°, 10°, 17° (baseline
aktual), dan 30° berdasarkan parameter specific yield serta metrik
evaluasi statistik seperti MAPE, RMSE, koefisien korelasi, dan koefisien
determinasi (R2).
Hasil penelitian menunjukkan model simulasi PVsyst sangat akurat dengan
deviasi tahunan 0,4?n MAPE harian 3,56% (R2=0,979) pada tahun
baseline 2021, serta tetap andal selama de-rating 2025 dengan rata-rata
kesalahan global (MAPE bulanan) sebesar 4,24%. Integrasi tren membuktikan
keselarasan simulasi dan eksperimen, di mana konfigurasi sudut 10° menunjukkan
kesesuaian performa tertinggi (R2=0,93) terhadap baseline dan
ditetapkan sebagai kondisi optimum untuk lokasi geografis Makassar (-5,22° LS).
Sudut ini menghasilkan produksi tahunan tertinggi sebesar 54.229 kWh/tahun dan specific
yield 1075,97 kWh/kWp/tahun, atau setara dengan peningkatan gain
energi 0,61?ri kondisi eksisting.
Solar Power Plant (PLTS) implementation in
tropical regions faces challenges from microclimate fluctuations and high
module operating temperatures that can reduce solar cell efficiency. This study
aims to analyze the influence of the tropical climate on PLTS performance,
model a 50-kWp on-grid PLTS system at UPDL Makassar using PVsyst, and evaluate
the consistency of performance trends through an experimental unit to determine
the optimum fixed-tilt angle for maximizing energy yield.
The research methodology employs a
quantitative approach with an experimental-simulative method. The performance
of the main 50-kWp system was evaluated using 2021 historical data and 2025
temporal verification data during capacity de-rating conditions. Simultaneously,
a 1-kWp experimental unit was utilized to observe relative performance trends
across varying tilt angles of 5°, 10°, 17° (actual baseline), and 30° based on
specific yield parameters and statistical evaluation metrics, including MAPE,
RMSE, correlation coefficient, and coefficient of determination (R2).
The results indicate that the PVsyst
simulation model is highly accurate, showing an annual deviation of only 0.4%
and a daily MAPE of 3.56% (R2 = 0.979) for the 2021 baseline year,
while remaining reliable during the 2025 de-rating with a global average error
(monthly MAPE) of 4.24%. Trend integration demonstrates clear alignment between
simulation and field experiment, where the 10° tilt configuration exhibits the
highest performance consistency (R2 = 0.93) relative to the baseline
and is established as the optimum condition for Makassar's geographical
location (-5.22° S). This angle yields the highest annual generation of 54,229
kWh/year and a specific yield of 1,075.97 kWh/kWp/year, equivalent to a 0.61%
energy gain over the existing configuration.
Kata Kunci : PLTS On-grid, Sudut Kemiringan Optimum, PVsyst, Iklim Tropis, Specific Yield / On-grid PV, Optimum Tilt Angle, PVsyst, Tropical Climate, Specific Yield.