STUDI PENINGKATAN PERFORMANCE COOLING TOWER TIPE FORCED DRAUGHT COUNTER FLOW DENGAN MENGGUNAKAN SISTEM HYBRID

Arvin, Prof. Ir. Samsul Kamal, M.Sc., Ph.D

2010 | Tesis | S2 Teknik Mesin

Studi peningkatan performa forced draught counter flow wet cooling tower dengan cara mengatur kondisi udara pendingin sebelum memasuki cooling tower telah dipelajari secara eksperimen menggunakan sistem hybrid. Penambahan sebuah heat exchanger unit tipe cross flow water to air dengan dimensi 48,5 x 34,5 x 5,5 cm3 pada daerah sebelum sisi inlet cooling tower digunakan untuk mensimulasikan kondisi hybrid. Cooling tower dengan film evaporation type yang memiliki luas penampang 32 x 32 cm2 dan tinggi packing 50 cm digunakan pada eksperimen ini. Kondisi udara pendingin dengan 20°-28°C dry bulb temperature (Tdb) dan 65-85% Relative humidity (?) digunakan pada eksperimen ini untuk mensimulasikan kondisi udara pada pagi, siang, dan malam hari. Disamping itu pada eksperimen ini temperatur air panas (Tw) juga divariasikan dari temperatur 44-52°C dengan perbandingan laju aliran massa air-udara (L/G) = 0,92-1,32. Dari hasil eksperimen ini didapatkan bahwa dengan penggunaan sistem hybrid efektivitas termal akan meningkat 3,47% pada kondisi Tdb = 20°C (? = 85%), Tw = 48°C dan L/G = 1,12. Peningkatan efektivitas termal pada kondisi ini akan menyebabkan penghematan biaya operasional sebesar Rp 19,97/jam.

Study of increase the performance of forced draught counter flow wet cooling tower with settle the cooling air conditions before enter the inlet of cooling tower had studied experimentally using hybrid system. In order to simulate the hybrid condition, an addition of cross flow water to air heat exchanger unit type with outside dimensions 48.5 x 34.5 x 5.5 cm3 is installed before the inlet of cooling tower. Film evaporation type of a cooling tower with 32 x 32 cm2 cross sectional area and 50 cm packing height is used in this experiment. To simulate air condition in the morning, noon, and midnight, cooling air with 20-28°C dry bulb temperature (Tdb) and 65-85% relative humidity (φ) is settled. In this experiment hot water temperature (Tw) is also varied from 44-52°C with ratio of water-air mass flow rate (L/G) = 0.92-1.32. The result is thermal effectiveness will increase 3.47% at Tdb = 20°C, φ = 85% cooling air condition, Tw = 48°C, and L/G = 1.12. The increase of thermal effectiveness will decrease the cooling tower operational cost about Rp 19.97 / hour.

Kata Kunci : cooling tower, hybrid, efektivitas termal

  1. S2-FTK-2010-Arvin-abstract.pdf  
  2. S2-FTK-2010-Arvin-bibliography.pdf  
  3. S2-FTK-2010-Arvin-tableofcontent.pdf  
  4. S2-FTK-2010-Arvin-title.pdf