Desain Perkuatan Secant Pile Menggunakan Angkur Pada Proyek Pembangunan Rumah Sakit Ibu Dan Anak Dr. Hasan Sadikin Bandung
Ricario Succes, Dr. Eng. Fikri Faris, ST., M.Eng.
2024 | Skripsi | TEKNIK SIPIL
Proyek Pembangunan Rumah Sakit Ibu dan Anak Dr. Hasan Sadikin berupa sebuah gedung bertingkat yang memiliki 8 lantai ditambah 1 lantai basement. Basement di Rumah Sakit Ibu dan Anak Dr. Hasan Sadikin digunakan sebagai tempat parkir. Basemen tersebut dilengkapi dengan pit lift dan ground water tank sehingga dasar galian basement yang direncanakan memiliki elevasi yang tidak rata dan terdapat lereng-lereng yang menghubungkan antara elevasi yang berbeda-beda tersebut. Untuk melindungi galian basement, dinding penahan tanah dengan jenis secant pile diletakkan di pinggir galian basement. Penelitian ini bertujuan untuk menganalisis stabilitas secant pile serta mendesain perkuatan berupa angkur apabila diperlukan.
Proyek berlokasi di Jl. Pasteur No. 38, Pasteur, Kecamatan Sukajadi, Kota Bandung, Jawa Barat. Data yang digunakan merupakan data sekunder yang diambil dari proyek. Data yang digunakan berupa data penyelidikan lokasi, gambar shopdrawing, data profil dan mutu material yang digunakan, serta data bangunan eksisting di sekitar lokasi proyek. Parameter yang dibutuhkan untuk pemodelan didapatkan dari pengolahan ulang hasil penyelidikan lokasi, serta informasi seputar bidang tinjauan yang didapatkan dari dokumen resmi serta pengamatan langsung. Metode yang digunakan adalah analisis elemen hingga dengan perangkat lunak Plaxis 2D.
Berdasarkan hasil analisis, stabilitas secant pile tanpa perkuatan angkur tidak memenuhi standar. Oleh karena itu, diusulkan untuk memperkuat stabilitas secant pile dengan perkuatan berupa angkur. Berdasarkan hasil rancangan, desain angkur memiliki sudut 30 derajat, panjang unbond length 6,5 m, panjang bond length 3,7 m, dan spasi horizontal 1,5 m yang menghasilkan nilai SF global = 2,611, defleksi horizontal maksimum secant pile = 53,93 mm, dan momen retak beton secant pile = 192,98 kNm.
Dr. Hasan Sadikin’s Mother and Child
Hospital Construction Project is a multi-storey building which has 8 floors
plus 1 basement floor. The basement at Dr. Hasan Sadikin’s Mother and Child
Hospital is used as a parking area. The basement is equipped with a pit lift
and ground water tank so that the base of the planned basement excavation has
an uneven elevation and there are slopes that connect the different elevations.
To protect the basement excavation, a retaining wall with a secant pile type is
placed at the edge of the basement excavation. This research aims to analyze
the stability of the secant pile and design reinforcement in the form of
anchors if necessary.
The project is located on Jl. Pasteur No.
38, Pasteur, Sukajadi District, Bandung City, West Java. The data used is
secondary data taken from the project. The data used is in the form of site
investigation data, shop drawings, profile and quality of materials used, as
well as existing building data around the project location. The parameters
required for modeling are obtained from reprocessing the results of site
investigations, as well as information about the field of review obtained from
official documents and direct observations. The method used is finite element
analysis with Plaxis 2D software.
Based on the analysis
results, the stability of the secant pile without anchor reinforcement does not
meet the standards. Therefore, it is proposed to strengthen the stability of
the secant pile with reinforcement in the form of anchors. Based on the design
results, the anchor design has an angle of 30 degrees, an unbond length of 6.5
m, a bond length of 3.7 m, and a horizontal spacing of 1.5 m which produces a
global SF value = 2.611, maximum horizontal deflection of the pile secant = 53,
93 mm, and the concrete cracking moment of the secant pile = 192.98 kNm.
Kata Kunci : Galian Basement, Secant Pile, Angkur Tanah, Plaxis 2D