Perancangan Sisten Otomasi Proses Stasiun Kerja Modular Production System of Automation Processes (MPS AP) Festo
Achmad Bayu Firdaus, Dr.-Ing. Ir. Awang Noor Indra Wardana, S.T., M.T., M.Sc., IPM., Dr.Eng. Dwi Joko Suroso S.T., M.Eng.
2023 | Skripsi | FISIKA TEKNIK
Sistem otomasi proses pada industri mengami kemajuan pesat dalam
beberapa dekade terakhir. Salah satu media pembelajaran sistem otomasi proses
adalah stasiun kerja modular production
system of automation processes (MPS AP).
Meskipun demikian, belum ada penelitian spesifik terkait perancangan otomasi
proses pada stasiun kerja MPS AP. Maka dari itu, penelitian ini merancang
otomasi proses pada stasiun kerja MPS AP secara
sederhana.
Penelitian ini menitik beratkan pada perancangan stasiun kerja MPS AP
menggunakan PID kontroler 1516 PN/DP untuk merancang otomasi proses dengan 3
(tiga) skema yaitu ketinggian, laju aliran, dan tekanan fluida. Penelitian ini dilakukan
secara bertahap, dimulai dengan studi literatur, observasi stasiun kerja MPS AP,
analisa kebutuhan sistem, perancangan sistem, pengujian sistem dan analisis
hasil pengujian lalu diakhiri dengan penulisan laporan penelitian.
Hasil perancangan diuji dengan 5 (lima)
parameter respon transien pada PID kontroler: waktu naik, waktu
puncak, waktu penetapan, persen lewatan, dan galat keadaan tunak. Sebagai
contoh, hasil analisis galat keadaan tunak untuk ketinggihan fluida, laju
aliran fluida, dan tekanan fluida adalah 1,45%, 0,35%, dan 0,12%. Dilihat dari
hasil uji galat keadaan tunak dan empat parameter lainnya, dapat disimpulkan
bahwa 3 skema perancangan telah memenuhi tuntutan perancangan.
Process automation systems in industry have experienced rapid progress
in the last few decades. One of the learning media for process automation
systems is the modular production system of automation processes (MPS AP)
workstation. However, specific research on process automation design at MPS AP
workstations has yet to be conducted. Therefore, this research designs simple
process automation at the MPS AP workstation.
This research focuses on designing an MPS AP workstation using a PID
controller 1516 PN/DP to design process automation with 3 (three) schemes:
height, flow rate, and fluid pressure. This research was carried out in stages,
starting with a literature study, observing MPS AP workstations, system
requirements analysis, system design, system testing, and analysis of test
results, and ending with writing a research report.
The design results were tested with 5 (five) transient response
parameters on the PID controller: rise time, peak time, settling time, percent
overshoot, and steady-state error. For example, the steady-state error analysis
results for fluid height, fluid flow rate, and fluid pressure are 1.45%, 0.35%,
and 0.12%, respectively. From the steady-state error test results and four other
parameters, it can be concluded that the three design schemes have met
the design demands.
Kata Kunci : Otomasi, proses, kontrol, stasiun kerja MPS AP