ANALISIS DAMPAK PUTUSNYA PENGHANTAR NETRAL TERHADAP SISTEM PROTEKSI RECLOSER M4-545-166 PENYULANG TMG 05 P.T PLN (Persero) ULP PARAKAN

MUSTOFA HERDIATMAJA, Nur Sulistyawati, S.T., M.T.

2019 | Tugas Akhir | D3 TEKNOLOGI LISTRIK

Proteksi merupakan salah satu komponen penting dalam sistem distribusi tenaga listrik, dalam sistem tenaga listrik proteksi digunakan untuk menjaga keandalan, kontinutitas pelayanan dan keamanan terhadapan lingkungan. Pada sistem distribusi tenaga listrik yang menggunakan sistem Bintang 4 kawat Multy Grounded Common Neutral (Y-4W-MGCN), jika kawat netral hilang sistem tersebut memiliki kelemahan. Sehingga hilangnya kawat netral dibeberapa tempat pada saluran yang menguunakan sistem Y-4W-MGCN merupakan suatu kondisi tidak normal dan menyebabkan beberapa resiko terhadap lingkungan serta terhadap performance operasi sistem distribusi tenaga listrik dan kualitas pelayanan beban di sisi pelanggan. Seperti yang terjadi pada recloser M4-545-166 penyulang Temanggung 05 yang gagal melakukan proteksi ketika terjadi kabel fasa menyentuh tanah saat bencana alam, yaitu Ground Fault Relay tidak mau bekerja. Dengan analisis yang telah dilakukan dapat ditarik kesimpulan bahwa putusnya penghantar netral mempengaruhi sensitifitas kinerja dari Ground Fault Relay pada sistem proteksi yang menggunakan sistem Y-4W-MGCN. Hasil akhir yang didapatkan yaitu berupa analisis dampak dari hilangnya penghantar netral pada sistem Y-4W-MGCN yaitu mempengaruhi besarnya nilai Zo eq yang seharusnya sesuai dengan datasheet kabel 150 mm2 yaitu sebesar 20,1324 + j 36,99264 ohm akibat penghantar netral di sepanjang penyulang hilang, nilai impedansi berubah menjadi 101,7870 + j 14,3958 ohm, hal ini yang menjadi penyebab kegagalan proteksi GFR pada recloser M4-545-166.

Protection is one essential component of, electricity distribution system in the electricity used to keep the reliability of, protection kontinutitas terhadapan. environment and security servicesIn electricity distribution system that uses star systems 4 wire multy grounded common neutral ( Y-4W-MGCN ), if the system lost neutral wire. have weaknessesLoss of wire and a place in the neutral along feeder using Y-4W-MGCN system is a condition not normal and cause some risk to the environment and on the performance of the operation of a system distrbusi electricity and service quality. burden with customers as is the case with recloser M4-545-166 feeder temanggung 05 who failed to protection in the cable in phase short with the ground while, natural disasters the ground fault. With analysis that has been done can be drawn the conclusion that penghantar neutral with affect sensitivity the performance of ground fault relay on system protective use the Y-4W-MGCN . The last result obtained in the form of an analysis of the impact from the loss of conductor neutral on a system Y-4W-MGCN that is affecting the magnitude of the Z0eq which are supposed to correspond with datasheet cable 150 mm2 is as much as 20,1324 + j 36,99264 ohm due to conductor neutral along feeder missing , value impedance turned into 101,7870 + j 14,3958 ohm , this that causes failure protection gfr in recloser M4-545-166 .

Kata Kunci : Ground Fault Relay, keandalan, kontinuitas, proteksi, relay, recloser, datasheet Y-4W-MGCN.

  1. D3-2019-401635-abstract.pdf  
  2. D3-2019-401635-bibliography.pdf  
  3. D3-2019-401635-tableofcontent.pdf  
  4. D3-2019-401635-title.pdf