PENGARUH PENAMBAHAN DISTRIBUTED GENERATOR TERHADAP SETTING DIRECTIONAL OVER CURRENT RELAY (DOCR) PADA SISTEM DISTRIBUSI CLOSED LOOP 9 BUS
YUDAN RUDI WIDAYANTA, Harnoko St., Ir., M.T. ; Sasongko Pramono Hadi, Prof. Dr., Ir., DEA
2018 | Skripsi | S1 TEKNIK ELEKTRODesain feeder merupakan salah satu hal yang mempengaruhi tingkat keandalan suatu sistem tenaga listrik. Banyak jaringan distribusi saat ini yang dioperasikan sebagai closed loop untuk meningkatkan keandalan penyaluran tenaga listrik. Desain feeder yang handal harus diimbangi dengan desain proteksi yang handal pula. Perancangan sistem proteksi dilakukan pada tingkat koordinasi menggunakan rele Directional Over Current Relay (DOCR). Dalam pengembangan sistem tenaga listrik dapat dipastikan bahwa akan ada penambahan pembangkit baru yang masuk ke dalam sistem distribusi closed loop. Penambahan pembangkit tersebut akan merubah besar arus hubung singkat yang ada di setiap titik. Oleh karena itu diperlukan resetting pada DOCR sehinga rele tetap bekerja secara koordinatif dan selektif. Pada hasil analisis simulasi, ditemukan beberapa kesalahan pada operasi rele setelah penambahan DG. Sebagai contoh gangguan hubung singkat pada Saluran 2 menyebabkan Rele 5, rele 6, dan Rele 7 salah beroperasi. Hal ini dikarenakan besar arus hubung singkat bertambah besar dari 2.92 kA menjadi 3.50 kA. Waktu kerja rele baik sebelum maupun sesudah penambahan DG untuk rele utama bekerja pada waktu 0.05 detik dan rele backup 0.35 detik.
Feeder design is one of the things that affects the level of reliability of an electric power system. Many distribution networks are operated as closed loops to improve the reliability of electricity distribution. A reliable feeder design must be balanced with a reliable protection design. The protection system design is carried out at the level of coordination using Directional Over Current Relay (DOCR) relays. In the development of the electric power system it can be ascertained that there will be additional new power plants that enter the closed loop distribution system. The addition of the power plant will change the amount of short circuit current at each point. Therefore, it is necessary to resetting DOCR so that the relay continues to work coordinatively and selectively. In the results of the simulation analysis, several errors were found in the relay operation after the addition of DG. For example a short circuit fault on Saluran 2 causes Rele 5, Rele 6, and Rele 7 to operate incorrectly. This happens because the short circuit current increases from 2.92 kA to 3.50 kA. The relay working time does not change either before or after the addition of DG for the main relay works at 0.05 seconds and the relay backup is 0.35 seconds.
Kata Kunci : Sistem proteksi, koordinasi proteksi, closed loop, directional over current relay