KOORDINASI PROTEKSI ANTAR FUSE CUT OUT (FCO) JARINGAN DISTRIBUSI FASE TUNGGAL PENYULANG WONOSARI 2 PT. PLN (PERSERO) RAYON DELANGGU UNTUK MEMINIMALISIR DAERAH PADAM

ARIO BIMA TRI W, Atikah Surriani, S.T.,M.Eng.

2018 | Tugas Akhir | D3 TEKNOLOGI LISTRIK

Distribusi jaringan satu fase merupakan jaringan cabang dari jaringan distribusi jaringan tiga fase. Distribusi jaringan satu fase sering terjadi gangguan hubung singkat satu fase. Gangguan tersebut diakibatkan oleh berbagai hal seperti pohon, burung merpati, ular, kadal dan lain-lain. Arus hubung singkat nilainya sangat besar. Jika tidak diproteksi dengan baik dapat menyebabkan Recloser trip. Hubung singkat tersebut dapat menyebabkan gangguan permanen, untuk itu diperlukan pemadaman dan perbaikan untuk mengatasi gangguan. Distribusi jaringan satu fase terdapat sebuah peralatan proteksi yaitu Fuse Cut Out (FCO). Jaringan satu fase biasanya terdapat minimal satu FCO. Jika jaringan satu fase memiliki lebih dari satu FCO, FCO dipasang disisi hilir dan hulu. Dengan adanya lebih dari satu FCO yang terpasang diperlukan koordinasi yang baik antar FCO, agar saat terjadi gangguan permanen dapat mengurangi daerah padam. Koordinasi gangguan pertama cukup baik karena fuselink yang terpasang pada tiang K1-19O/1. Arus gangguan yang terjadi pada gangguan pertama sebesar 1144,074186 A dengan fuselink yang terpasang sebesar 30 A. Gangguan kedua, FCO K1-35/1 berkerja dengan baik dengan memutuskan fuselink FCO tiang K1-35/1. Tetapi pada gangguan ini tidak memerlukan koordinasi karena hanya terdapat satu FCO saja yang terpasang. Arus gangguan yang terjadi pada gangguan ini sebesar 1144,074186 A dengan fuselink yang terpasang sebesar 15 A. Gangguan ketiga terdapat koordinasi antara FCO jaringan satu fase dengan jaringan tiga fase karena pada jaringan tiga fase di tiang K1-281/64B. Koordinasi antar FCO kurang baik, karena pada FCO tiang K1-56/16 tidak memutus sehingga membuat FCO jaringan tiga fase yang berkerja. FCO K1-56/16 tidak putus karena FCO tidak menggunakan fuselink melainkan kabel konduktor yang jelas sangat berbeda dengan fuselink. Arus gangguan yang terjadi pada gangguan ketiga sebesar 2689,278286 A.

Single phase network distribution is the branch of three phase network distribution. Single phase network often occurs disruption from single phase short circuit. The interference causes by many thing such as lizard, pigeons, snake, branch of trees, etcetera. Short circuit current has very large. If the protection not protect the short circuit current very well, it can be cause recloser trip. Short circuit can makes permanent disruption, so it required to blackout and repair to overcome the disruption. Single phase network has component protection, it called Fuse Cut Out. Single phase network at least has one fuse cut out. If the single phase network has more than one fuse cut out, it will be installed on the upstream and on downstream. If the single phase network has more than one fuse cut out, they need coordination between the fuse cut out. The coordination is very important cause if the fuse cut out doing very well, when the system occur permanent disruption it can be minimize blackout area. In first disruption, coordination between fuse cut out was very well because a fuse cut out installed on pole K1-19O/1 was break. A short circuit current amount of 1144,074186 A, and a fuselink installed by 30 A. In second disruption, fuse cut out installed on pole K1-35/1. On this disruption not need coordination between fuse cut out, because it just installed by one fuse cut out. A short circuit current amount of 1144,074186 A and a fuselink has installed by 15 A. in third disruption need coordination between single phase network fuse cut out and three phase network fuse cut out, third phase network fuse cut out installed on pole K1-281/64B and single phase network fuse cut out installed on K1-56/16. When the disruption occurs, a single phase fuse cut out was not working. But three phase fuse cut out was working very well and break the fuselink. A single phase fuse cut out not working because, the fuselink was replace another cable. A tire wire and fuselink is very different. So when the disruption occurs, tire wire did not break. Short circuit current in third disruption amount of 2689,278286 A.

Kata Kunci : Kata kunci : Jaringan distribusi satu fase, jaringan distribusi tiga fase gangguan hubung singkat, Fuse Cut Out (FCO).

  1. D3-2018-386444-abstract.pdf  
  2. D3-2018-386444-bibliography.pdf  
  3. D3-2018-386444-tableofcontent.pdf  
  4. D3-2018-386444-title.pdf